JUPITER INTEGRATED SENSOR SYSTEMS PVT. LTD.
Air Velocity Transmitter for Measurement

Air Velocity Transmitter for Measurement

Send Inquiry

EE66 air velocity transmitter series are designed for high accuracy measurement of lowest air velocities. It is the ideal solution for laminar flow control and special ventilation applications. The E+E thin film sensor is operating on an innovative hot film anemometer principle. This guarantees excellent accuracy for air velocity down to almost 0m/s, which is not possible for conventional anemometers with commercial temperature sensors or NTC bead thermistors. The E+E sensor is much more insensitive to pollution than all other anemometer principles. This increases reliability and reduces maintenance costs. EE66 series are available with current or voltage output, the measuring range and the response time can be selected with jumpers by the user. Low angular dependence enables easy, cost-effective installation.

An integrated LC display and a version with remote sensing probe are also available.

Typical Applications :

  • Clean room control
  • Laminar flow control

Features :

  • Measurement down to 0 m/s
  • Low angular dependence
  • Easy installation

Technical Data :

Measuring values 1)


Working range

0...1m/s (0...200ft/min)
0...1.5m/s (0...300ft/min)
0...2m/s (0...400ft/min)

Output 1)

0 - 10 V -1 mA < IL < 1 mA
4 - 20 mA RL< 450 Ω

Accuracy at 20 degC (68oF), 45 % RH and 1013hPa

0...1m/s (0...200ft/min) + (0.04m/s / 7.9ft/min + 2 % of m. v.)
0...1.5m/s (0...300ft/min) + (0.05m/s / 9.8ft/min+ 2 % of m. v.)
0...2m/s (0...400ft/min) + (0.06m/s / 11.8ft/min+ 2 % of m. v.)

Response time τ90 1) 2)

typ. 4 sec. or typ. 0.2 sec. (at constant temperature)

General

Power supply

SELV 24V AC/DC ± 20 % SELV = Safety Extra Low Voltage

Current consumption
for AC supply
for DC supply


max. 150 mA
max. 90 mA

Angular dependence

< 3 % of measurement at | ∆α | < 10o

Cable gland

M16x1.5 cable Ø 4.5 - 10 mm (0.18 - 0.39 inch)

Electrical connection

screw terminals max. 1.5 mm2 (AWG 16)

Electromagnetic compatibility

EN 50081-1
EN 50082-1 EN 50082-2

Housing/protecting class

Polycarbonat / IP65, Nema 4 with LC display IP40

Temperature range

working temperature probe -25...50 degC (-13...122oF)
working temperature electronic -10...50 degC (14...122oF)
storage temperature -30...60 degC (-22...140oF)