0

HygroFlex 5 Series

HygroFlex 5 Series
HygroFlex 5 Series
Price And Quantity
  • 1
  • Piece/Pieces
  • 6000.00 - 35000.00 INR
Product Specifications
  • For HVAC Applications, Building Management Systems, Museums and Libraries
  • Transmitter
  • Metal
  • 10-28 Volt (v)
  • 100-500 Grams (g)
  • Electronic
    Product Description

    The HygroFlex5 Series offers you ultimate performance and flexibility thanks to its interchangeable HygroClip2 probes. The transmitters come in wall and duct mount versions. Many useful functions can be accessed with optional HW4 software. HF5-Series is available with analog and digital outputs, so compatibilty with almost any monitoring or control system is assured. Digital versions may be networked togther to form a dedicated environmental monitoring system using HW4 software. The new generation device not only has a unique calibration and adjustment process, but also allows probes to be interchanged in just a few seconds. This easy interchangeability during operation reduces down-time and service costs to a huge extent. The possibility of using every probe as a simulator with fixed output values is a big advantage for system validation. In the case of networked devices this can even be carried out online from a remote PC workstation.

    Applications

    • High specification HVAC applications, building management systems, museums, libraries, environmental monitoring systems.

    Highlights :

    • Unique calibration and adjustment process
    • Highest reproducibility
    • Wall and duct versions; the wall version also serves for the connection of cable based probes
    • Many useful functions can be activated with the optional HW4 software

    HF5 wall & duct versions

    Applications

    • HVAC applications, building management systems, museums, libraries, etc.

    Highlights and common features

    • Probe interchangeable in just a few seconds
    • Measures relative humidity, temperature and dew/frost point
    • Calculates all psychrometric values
    • Range of application -40…60 oC; -10…60oC with LCD, 0…100 %rh
    • Automatic sensor test & drift compensation
    • Use as a simulator for system validation
    • UART service interface
    • Precision: dependent on the probe and adjustment profile used
    • Can be mounted on a DIN rail (see accessories, page 102)
    • Suitable probes: all HygroClip2 (HC2x) probes

    Includes flange for duct mounting :

    Wall version

    HF52-W series

    HF53-W series

    Type

    2- or 2 x 2-wire

    3/4-wire

    Signals

    Signals freely scalable

    Signals freely selectable and scalable

    Features

    Alarm indicators, display and keypad (optional) Optional USB & RS485 interface


    Duct version

    HF52-D series

    HF53x-D series

    Type

    2- or 2 x 2-wire

    3/4-wire

    Signals

    Signals freely scalable

    Signals freely selectable and scalable

    Features

    Alarm indicators, display and keypad (optional) Optional USB & RS485 interface

    Technical Specification :

    Power supply / Connections

    HF52

    HF53

    Supply voltage

    10…28 VDC, 4…20 mA current loop
    V min = 10 V + (0.02 x load*)

    15…40 VDC /12…28 VAC
    at 500 Ω

    Current consumption

    2 x 20 mA

    <50 mA

    Electrical connections

    Screw terminals and M16 cable gland or 1/2" conduit adapter

    Humidity measurement

    HF52

    HF53

    Sensor

    ROTRONICHygromer®IN-1 (depending on the HygroClip2 used)

    Measurement range

    0…100 %rh

    Accuracy at 23 oC

    + 0.8 %rh (probe dependent)

    Repeatability

    0.3 %rh

    Long term stability

    <1 %rh/year

    Response time

    Typically 10 s for 63 % of a jump 35 - 80 %rh (1 m/sec air flow at sensor)

    Temperature measurement

    HF52

    HF53

    Sensor

    Pt100 1/3 Class B (in all HygroClip2 probes)

    Measurement range

    -100…200 oC / -148…392 oF

    Accuracy at 23 oC

    +0.1 K (probe dependent)

    Repeatability

    0.05 oC

    Long term stability

    <1 oC/year

    Response time

    Typically 4 s for 63 % of a change from 23 to 80 oC (1 m/sec air flow at sensor)

    Calculated parameters

    HF52

    HF53

    Psychrometric calculations

    All types available

    Start-up time

    Typically 3.4 s

    Typically 1.9 s

    Signal type (selectable by jumper)

    4…20 mA

    0…20 mA, 4…20 mA , 0…1 V, 0… 5 V, 0…10 V

    Scale limits

    -999.99…+9999.99 units, user scaleable

    Maximum load (in Ω)

    0/500 Ω

    0/500 Ω (current signal), min. 1000 Ω (voltage signal)

    Type of interface

    USB or Ethernet TCP/IP (cable connection or wireless) & RS485

    Service interface

    UART (universal asynchronous receiver transmitter) on mini USB connector

    Service cable maximum length

    5 m (16.4 ft)

    Optional display

    LCD, 1 or 2 decimals, without backlight

    LCD, 1 or 2 decimals, with backlight and trend indicator

    Probe material

    Polycarbonate

    Filter material

    Polyethylene

    Housing material / Protection

    ABS / IP 65 (except for models with USB interface)

    Weight

    Approx. 250 g

    CE/EMC compatibility

    EMC Directive 2004/108/EC

    EN 61000-6-1: 2001, EN 61000-6-2: 2005

    EN 61000-6-3: 2005, EN 61000-6-4: 2001 + A11

    Solder

    Lead free (RoHS-compliant)

    Fire resistance

    Conforms to UL94-HB

    FDA/GAMP compatibility

    Conforms to FDA 21CFR Part 11 and GAMP4

    Electronics operating range

    -40…60oC / (models with display: -10…60 oC) 0…100 %rh, non-condensing

    Maximum wind velocity at probe

    40 m/s (7,870 ft/min)

    Trade Information
    • Cash in Advance (CID), Cash Advance (CA)
    • 100 Per Week
    • 3 Days
    • Yes
    • Sample costs shipping and taxes has to be paid by the buyer
    • All India
      Contact Us

      401 & G-414-416 A Wing, Kailash Indl. Complex, Near Dynalog, Behind Godrej Colony, Park Site, Vikhroli (West), Mumbai, Maharashtra, 400079, India
      Phone :+918068210843